1.Whole installation of transmitter and flow element can save installation and maintenance workload.
2.Integral orifice plate adopts inner polished straight pipe section, upstream with 20 times pipe diameter, downstream with 10 times pipe diameter, can achieve good rectification effect and reduce the uncertainty of measurement.
3.High accuracy and the basic error of integral orifice flow meter calibrated by real flow can reach up to ±0.5%.
4.Tap body is made of stainless steel forgings, which ensures the overall strength and minimizes the possible leakage points.
Nominal Diameter: 1/2″(DN15)、3/4″(DN20)、1″(DN25)、1-1/2″(DN40)
Nominal Pressure: 10.0MPa、CL600
Medium Temperature: Integrated installation is less than 150℃ and split installation is less than 454℃
Output Signal: 4~20mA+HART
Accuracy: ±1.5~2.5% (Actual flow calibration can be up to ±0.5%)
Repeatability: 0.2%
Turndown: 10:1
Explosion-proof Type: Ex iaⅡCT4; Ex dⅡCT6
IP Rating: IP67
Refining: Hydrocracking
您的浏览器当前宽度低于1100px;请使用1300px以上宽度访问。